Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T17FC00705
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2017 | FIRE SPKLR - FINAL | Approved | ||
| 10/06/2017 | FIRE SPKLR - FINAL | Partial Approval | 1) correct head in closet next to walk in cooler. Too far from ceiling. 2) Correct coverage in back of bar area. Upright to be moved up 3" and replaced by pendent. 3) Add head in elec. closet. 4) Correct coverage in back rooms. |