Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2017 |
FIRE - ALARM FINAL |
|
Approved |
|
| 06/23/2017 |
FIRE - ALARM FINAL |
|
Partial Approval |
Label Door "FACP". Need dedicated circuit. Need to verify loss of power and secondary power. Label circuit and add lockout. Remove all non-working SD throughout. Add enclosure around dedicated FA outlet. Add lockout for bell circuit. |