Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - FCON - Sprinkler - Final
Permit Number - T17FC00362
Inspection Description - COT - FCON - Sprinkler - Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2018 | COT - FCON - Sprinkler - Final | jvincent | Denied | Entered by JVINCEN1 - Walked all the bldgs. Need to trim out several heads, remove tape from several heads, replace a couple painted heads, straighten some heads that were leaning, add sprinkler head wrench, label inspectors test. Need to walk every bldg again and still need to do flow test and main drain test. Placed most FDC knox plugs. Closing out all other permits. Will keep this one open for all bldgs. Keep all notes under this permit. |