Permit: T17FC00316

Parcel: 12310001A


Addresses:

1501 N CAMPBELL AV


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T17FC00316

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2022 FIRE - ALARM FINAL Approved Case closed and final by order of the fire marshal.
04/09/2019 FIRE - ALARM FINAL Partial Approval Need to have the "fire pump room" sign added to the interior of the fire pump room. Need to test the fire sprinkler panel for proper operation.
6 lights in the Pavillion need to be replaced and re-tested on emergency power.
They are working on the BDA need to follow up with them regarding if the system made it through UL/FM
Need to add heads in the boiler room under the new duct work that was added.
Verify operation of new exhasut in med gas room
Verify no parking signs for fd access
04/09/2019 FIRE - ALARM FINAL Partial Approval The following door items need to be corrected/verified:
•340300A too tight in the middle not latching W&W
•150200B door is bowed.
•340300A too tight in the middle not latching W&W
•350370 Too tight in the middle W&W
340202 not latching W&W
340700 increase latch speed, hinge bind- SMART DOOR/ W&W
•350506A Shim for 1/8” reveal Dpr spw, Electric strike not working. W&W
•350509A missing push pad, increase the latch speed. W&W Hinge bind- Smart Doors to follow
•240300D too tight in the middle W&W
•240300A Vertical rod not retracting W&W
•250610 missing electric strike ECD
•250210 north doors needs to be latched W&W
04/08/2019 FIRE - ALARM FINAL Partial Approval Tested the fire alarm system. Confirmed that the smoke detectors were working properly. Confirmed that all fire smoke dampers operate like they are designed/programmed to. Tested the fire fighters smoke control panel. Jensen Hughes commisioned the smoke control system. Tested the operation of the printer in the fire command center. Elevator was commissioned by the state eleavtor inspector. Waterfllows and tampers were confirmed to the main FACP and offsite monitoring. Monitoring is not contact id but it is alarm, supervisory and trouble as the code requires. Tested the kitchen fire suppression system and confirmed signals to the FACP. Tested all Won and roll down fire doors. Complete the test of all self closing and mag fire doors. Needed to add notification to the "shared offices" that Banner added. Tested with the yesterday and confirmed the proper operation.
01/02/2019 FIRE - ALARM FINAL Partial Approval to re-open the permit
02/01/2018 FIRE - ALARM FINAL Partial Approval Temporoary for the CUP, Monitoring Via Simplex and two phone lines. Temporoary is a horn strobe system