Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2017 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | All 3 ok | |
| 05/19/2017 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | 210 psi | |
| 05/16/2017 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | All underground is approved to be covered. Hydro and flush are all that are left to complete | |
| 05/12/2017 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | ||
| 05/05/2017 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Middle section approved to fill. Still have the last area of about 100 ft to the building to inspect so that they can back fill last area. | |
| 05/02/2017 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Piping only - NO HYRDRO PERFORMED YET. Inspected from SW corner of 22,000 SF Retail ( TJ Max) on West side of complex to center of Center Building ( Ross) also 22,000 SF building - on the South side ( see contractors approved plans for orange highlighting. All angled joints were mega lugged. All joints covered. Tracer wire is on C-900. 3 Feet plus a few extra inches deep. No pressure test performed yet. May back fill up to the joint were you will be connecting, but leave that joint open for viewing upon next inspection. |