Inspection History Details
Inspection Status: Closed
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2022 | FIRE - ALARM FINAL | Closed | PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED. | |
| 12/28/2021 | FIRE - ALARM FINAL | Cancelled | to re-open the permit | |
| 07/18/2017 | FIRE - ALARM FINAL | Partial Approval | repair/replace two tamper switches/modules. Correct the fire alarm drawings prior to calling in fire final again. West waterflow 49 seconds East waterflow 44 seconds Tested, smoke detector, manual pull station, kitchen fire suppression system, monitoring, ground fault, battery loss, AC power fail. Approved minus the tamper switches. |