Inspection History: FIRE - ALARM FINAL

Permit Number - T17FC00188

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Closed

Date Description Inspector Results Comments
10/13/2022 FIRE - ALARM FINAL Closed PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED.
12/28/2021 FIRE - ALARM FINAL Cancelled to re-open the permit
07/18/2017 FIRE - ALARM FINAL Partial Approval repair/replace two tamper switches/modules. Correct the fire alarm drawings prior to calling in fire final again.
West waterflow 49 seconds
East waterflow 44 seconds
Tested, smoke detector, manual pull station, kitchen fire suppression system, monitoring, ground fault, battery loss, AC power fail. Approved minus the tamper switches.