Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T17FC00178
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2017 | FIRE - ALARM FINAL | Approved | reverified the notification and flows: Flow 2 40 seconds Flow 4 55 seconds Flow 6 58 seconds Could not verify Flow 1 but Fireworx stated it was around 50 seconds. |
|
09/28/2017 | FIRE - ALARM FINAL | Partial Approval | Flow 1 = 102.5 Seconds Flow 2 = 23.6 Seconds Flow 3 = 44.2 Seconds Flow 4 = 30.3 Seconds Flow 5 = 40.2 Seconds Flow 6 = 29.8 Seconds 9 tampers are ok Duct Smoke are ok Monitoirng Confirmed Add visual devices over the moveable rack storage Add/move av's to the isle in front of the pharmacy and also by the cosmetics Lp1 Dv 1- 5 need to be either lowered to below duct work and or replaced with 175 candella Adjust the flow switches to be minimum 45 seconds |
|
07/27/2017 | FIRE - ALARM FINAL | Partial Approval | PA -Only item tested, tampers 1 & 4, and RTU #50 -Still need to test everything on plans -notification -smokes -door holds -waterflows -four more tampers -other RTU's approved if air balance reports on site and passed. -remove old system (all components and FACP) |