Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Closed
Inspection History: FIRE - ALARM FINAL
Permit Number - T17FC00050
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2022 | FIRE - ALARM FINAL | Closed | PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED. | |
08/29/2017 | FIRE - ALARM FINAL | Partial Approval | Need to perform the audibility and intellagibility test Need to install and test the fire sprinkler panel in the FCC Need to submit the ASBUILT drawings within two weeks. |
|
08/17/2017 | FIRE - ALARM FINAL | Partial Approval | Ok for T C O. Need to add four smoke detectors and sounders to the 4 large rooms with a living room. Need to replace smoke detector in the pool room with a heat detector. Need to provide documentation from JensenHughes that the smoke control system is approved and commissioned. Need to provide the Fire pump status indicators, sprinkler valve and water-flow detector display panels |