Permit: T17EL00234

Parcel: 138111660


Addresses:

6225 S DUNTON AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/06/2017 ELECTRIC - SERVICE UPGRADE Approved INC
08/30/2017 ELECTRIC - SERVICE UPGRADE Denied COMPLY WITH PREVIOUS
NEXT DENIAL WILL RESULT IN A REFEE
08/25/2017 ELECTRIC - SERVICE UPGRADE Denied METAL ADDRESS TAG
SEAL OPENINGS DEADFRONT
30 AMP WHITE LEAD TO BE BLACK OR RED (TAPE OK)
DOUBLE LUGED 50 AMP BREAKER
ALL BREAKERS TO MATCH PANEL TYPE
BOND WATER AND GAS LINES