Permit: T17EL00082

Parcel: 120020860


Addresses:

4000 S 15TH AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/24/2017 ELECTRIC - RECONNECT Approved RECN
04/07/2017 ELECTRIC - RECONNECT Denied MISSING SMOKE ALARMS BOTH SIDES OF BEDROOM DOORS FRONT UNIT
PANELS NOT LABELED WITH UNIT NUMBERS
UNITS NOT POSTED VISIBLE FROM STREET
PROVIDE PROPER CONNECTORS AT JNCTION BOX
OPEN CONDUCTORS IN J-BOX
04/05/2017 ELECTRIC - RECONNECT Denied PERMANENT LABEL SERVICE UNIT NUMBERS
POST UNIT NUMBERS VISIBLE FROM STREET
MIXED 40 AMP A/C BREAKER
WHITE HOT LEAD AT A/C CIRCUIT TO BE RED OR BLACK (TAPE OK)
MISSING SMOKE ALARMS BEDROOMS BOTH SIDES OF DOORS FRONT UNIT
NO ACCESS TO SUBPANEL/ SUBPANEL NT GROUNDED
SOME BEDROOM WINDOWS DO NOT MEET EGRESS STANDARDS