Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2017 |
ELECTRIC - FINAL |
|
Approved |
|
| 03/27/2017 |
ELECTRIC - FINAL |
|
Denied |
Label panel circuits. Outside receptacle to be GFI. Neutral not connected to bus bar. Ground to water connected above dilectric fitting. Install permanent address on panel. |