Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT IN GOOD STANDING ,, CLOSE CASE | |
| 04/04/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T18CM02294 ISSUED (T17DV06137 VALDEZ) ELECTRICAL REPAIRS | |
| 03/29/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | MEETING WITH DAN SANTA CRUZ AND MPH, PERMIT | |
| 03/27/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | T18CM02294 APPLIED PERMIT, MANAGER STATES HE IS WALKING PLANS THROUGH THIS WEEK | |
| 01/31/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | MEETING AT PDSD SEE CONDITIONS FOR DETAILS | |
| 01/23/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | NO PERMIT, DID SEND EMAIL TO MANAGER | |
| 12/05/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | INSPECTED UNIT EU , A HOUISE WITH AN ATTACHED SHED SERVICE LOCATION WITH MULTIPLE VIOLATIONS, NO GROUNDING SYSTEM, THE SYSTEM EXCEEDS MAXIMUN AMOUNT OF DISCONNECTING MEANS. NM VIOLATIONS. NO LABELING. WILL ADD TO NOV AND EMAIL TO OWNER AND MANAGER.. |
|
| 11/28/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | COMPLETED MOBILE HOME INSPECTIONS.. | |
| 11/24/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | INSPECTIONS CONTINUE: UNIT 41 HAS BURNT WIRING DUE TO IMPROPER CONNECT TO THE MAIN FUSE ON THE LINE SIDE.THIS CONNECT IS TO SUPPLY POWER TO A SEPARATE EQUIPMENT DISCONNET, POSSIBLE THE MINI SPLIT AC UNIT. THIS IS UNPERMITTED WORK. NOTICE AND ORDER POSTED ON THE FRONT DOOR OF UNIT 41, ALSO NOTIFIED MANAGER TO HAVE ELECTRICIAN REMOVE. I HAVE ROTATED FUSE TO OFF POSITION. | |
| 11/22/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | ELECTRICAL INSPECTIONS OF THE PARKS EQUIPMENT DISCONNECTS FOR UNITS 1 THRU 23, TO INCLUIDE THREE SERVICES. THERE ARE MULTIPLE ELECTRICAL VIOLATIONS.DETAIL NOTES WILL BE ADDED AFTER ALL UNITS HAVE BEEN INSPECTED. THE PARK DOES HAVE A ELECTRICIAN ONSITE REMOVING HAZARDS. WILL RESUME INSPECTIONS ON 11/24/2017. SUPERVISOR HAS BEEN UPDATED ON THECASE. | |
| 11/17/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | THE FOLLOWING UNITS HAVE BEEN SECURED BY HARDWARE OR BOARDING. 19, 21, 26, 35,42, 45 AND 47.. |