10/17/2017 INSP - INITIAL CODE ENFORCMENT Approved THE AIR CONDITIONING THE DISCONNECTING MEANS FOR THE AIR CONDITIONING UNIT ARE LOCATED INSIDE THE UTILITY ROOMS FOR ALL UNITS IN BUILDING 2 THE EQUIPMENT DISCONNECTS ARE NOT IN SIGHT VISIBILITY.

THE AIR CONDITIONING CONDENSERS LOCATED AT BUILDING 2 UNIT'S 2103 AND 2101 HAVE BEEN INSTALLED ON THE GROUND. THESE UNITS DO NOT MEET THE CLEARANCE OR INSTALL REQUIREMENTS.
THE GROUNDING ELECTRODE CONDUCTORS HAVE BEEN CUT AT BOTH SERVICES LOCATED AT BUILDING 8.

THERE HAS BEEN AN IRON FRAMED ASSEMBLY WITH NO DOORS INSTALLED AT THE END OF EACH SIDE OF THE BUILDING'S CORRIDOR. THIS ASSEMBLY WOULD CONTROL EGRESS. THE ASSEMBLY IS NOT FINISHED AT THIS TIME. THIS ASSEMBLY IN LOCATED AT BUILDING 2



BUILDING 1
EASTSIDE SERVICE, THE MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED
WESTSIDE SERVICE, THE MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED.
MISSING DEAD FRONT ON THE POOL EQUIPMENT DISCONNECT
UNUSED OPENINGS
MISSING CLAMP TO THE TO OVER HEAD RISER

BUILDING 2
THE NORTHSIDE SERVICE GROUNDING ELECTRODE CONDUCTED IS NOT PROPERLY SECURED TO THE BUILDING
MISSING HARDWARE AT THE SERVICE EQUIPMENT
REPLACE DECK BOARDS AS NEEDED
THE SOUTHSIDE SERVICE, MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED
MISSING CLAMP ON OVER HEAD RISER
GUTTER BOX UNUSED OPENINGS
ALL EXTERIOR LIGHT FIXTURES ARE NOT CODE COMPLIANT

UNIT 2103
THE GAS FURNACE HAS THE EXHAUST VENT PIPE DISCONNECTED FROM THE FURNACE.
WATER HEATER HAS NO DISCHARGE PIPE
A/C DISCONNECT NOT CODE COMPLIANT
DRYWALL REPAIR REQUIRED IN UTILITY ROOM

UNIT 2104
COLD WATER SHUT OFF MISSING HANDLE ON WATER HEATER
MISSING EXHAUST VENT PIPE TO GAS FURNACE
DRYWALL REPAIR REQUIRED IN UTILITY ROOM

UNIT 2208
COLD WATER SHUT OFF MISSING HANDLE ON WATER HEATER
WATER HEATER HAS NO DISCHARGE PIPE
DRYWALL REPAIR REQUIRED IN UTILITY ROOM

UNIT 2207
A/C DISCONNECT NOT CODE COMPLIANT
DRYWALL REPAIR REQUIRED IN UTILITY ROOM
WATER HEATER HAS NO DISCHARGE PIPE NOT CODE COMPLAINT.

UNIT 2102
LIGHT FIXTURE WALL PLATE HAS DETACHED FROM THE BUILDING, EXPOSED WIRES
CONDENSATE LINE NOT PLUMBED OUT THE BUILDING
A/C DISCONNECT NOT CODE COMPLAINT
DRYWALL REPAIR REQUIRED IN UTILITY ROOM
WATER HEATER HAS NO DISCHARGE PIPE

UNIT 2206

A/C DISCONNECT NOT CODE COMPLAINT
DRYWALL REPAIR REQUIRED IN UTILITY ROOM
WATER HEATER HAS NO DISCHARGE PIPE
CONDENSATE LINE NOT PLUMBED OUT THE BUILDING
DRYWALL REPAIR REQUIRED IN UTILITY ROOM

UNIT 2101

A/C DISCONNECT NOT CODE COMPLAINT DRYWALL REPAIR REQUIRED IN UTILITY ROOM
WATER HEATER HAS NO DISCHARGE PIPE NOT CODE COMPLAINT.
CONDENSATE LINE NOT CODE COMPLAINT
DRYWALL REPAIR REQUIRED IN UTILITY ROOM
WALL MOUNTED LIGHT FIXTURE HAS EXPOSED WIRING

UNIT 2205

A/C DISCONNECT NOT CODE COMPLAINT
DRYWALL REPAIR REQUIRED IN UTILITY ROOM
WATER HEATER HAS NO DISCHARGE PIPE

BUILDING 3

THE EASTSIDE SERVICE GROUNDING ELECTRODE CONDUCTOR IS NOT PROPERLY SECURED TO THE BUILDING
GUTTER BOX MISSING HARDWARE.

BUILDING 4

THE SERVICE GROUNDING ELECTRODE CONDUCTOR IS NOT PROPERLY SECURED TO THE BUILDING
THE CLAMP TO THE OVERHEAD RISER IS MISSING

BUILDING 5

THE WESTSIDE SERVICE, MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED

BUILDING 6

THE WEST SIDE 4 METERED PACK HAS MISSING MAIN BREAKER COVERS
THE EASTSIDE SERVICE, MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED
THE CLAMP TO THE OVERHEAD RISER IS MISSING
UNUSED OPENINGS IN THE GUTTER BOX

BUILDING 7

THE WESTSIDE SERVICE, MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED
THE EASTSIDE SERVICE, MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED
THE GROUNDING ELECTRODE CONDUCTOR IS NOT SECURED TO THE BUILDING

BUILDING 8

THE WESTSIDE SERVICE, MAIN DISCONNECTS FOR EACH UNITS ARE NOT PROPERLY LABELED