Case: T17DV03573

Parcel: 119046120


Addresses:

3733 S CLARK AV

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
09/28/2017 INSP - INITIAL CODE ENFORCMENT Approved UNIT B
UNIT B HAS MULTIPLE NON GROUNDING TYPE RECEPTACLES WHICH HAVE BEEN REPLACED WITH GROUNDING TYPE RECEPTACLES IN THE INTERIOR OF THE DWELLING.
ALL INTERIOR RECEPTACLES ARE LOOSE AND SOME ARE INOPERABLE
MULTIPLE OUTLETS HAVE MISSING COVER PLATES
THE REAR EXTERIOR DUPLEX RECEPTACLE HAS OPEN GROUND
THE NEW 125 AMP MAIN DISCONNECT FOR UNIT INSTALLED WITHOUT PERMIT
DRAIN PIPES UNDER THE KITCHEN SINK LEAK
NO SMOKE DETECTORS IN BEDROOMS
CEILING LIGHT FIXTURES IN BATHROOM AND BEDROOM HAVE THE GLOBES
FRONT PORCH BEAM HAS WOOD ROT (REPLACE) PERMIT
BATHROOM PEDESTAL SINK IN LOOSE.
GAS WATER HEATER: MISSING DISCHARGE PIPE
NOT PROPERLY INSTALLED
NO ENCLOSURE
EXHAUST VENT PIPE ZERO CLEARANCE FROM WOOD ROOF DECKING

UNIT 'S A AND B
THERE ARE TWO ROOF MOUNTED HVAC UNITS THAT HAVE BEEN INSTALLED WITHOUT PERMITS.
VERIFY GROUNDING SYSTEM
A KNOCK OUT OPENING IS BEING USED FOR THE GROUNDING ELECTRODE CONDUCTOR

UNIT A
THE MAIN DISCONNECT FOR UNIT A HAS UNUSED OPENINGS
NO LABELING
GAS WATER HEATER;
" LEAKS
" NO GAS SHUT OFF
" BODY HAS RUST
" NO DISCHARGE PIPE
" NO ENCLOSURE

T15CM06941 GAS PERMIT NOT FINAL AND IS EXPIRED