Case: T17DV03076

Parcel: 117111010


Addresses:

59 E PENNINGTON ST


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T17DV03076

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2017 INSP - INITIAL CODE ENFORCMENT Approved INSPECTION DID FIND MULTIPLE AREAS OF THE INTERIOR CEILING DAMAGED BY WATER, EVIDENCED BY SOAKED, DAMAGED DRYWALL, PAINT HOLDING WATER AND UPSTAIRS FOUND A 3 FT X 8 FT SECTION OF CEILING DRYWALL REMOVED DUE TO THE AMOUNT OF WATER DAMAGE.
ON THE ROOF I FOUND WATER PONDING IN BOTH THE S/E AND S/W CORNERS OF THE ROOF AROUND WHERE ROOF DRAINS WERE LOCATED, AND UNDER THE A/C UNIT. ROOF WAS CRACKED THROUGHOUT, ROOF COVERING WAS VERY SOFT, SPUNGY ALMOST AS IF 3-PLY ROOF COVERED A FOAM ROOF. WATER WAS CAUGHT UNDER THE ROOF COVERING AND OOZED OUT FROM UNDER THE TOP SHEET WHEN STEPPED UPON. I WAS ABLE TO RUB THE ROOF COVERING OFF WITH MY BOOT, SHOWING HOW SATURATED AND HOW MUCH WATER IS CAUGHT UNDER THE ROOF COVERING.