Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T17DV02184
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Found original hazardous 200 amp main electric service still in use. Tenant in unit 13 complained about some items in the unit. We asked if the panel was OK. We found hazardous electric sub panel still in use with added electric circuits exposed in side of the closet. We found exposed NM cables in the laundry room that was present at the first violation. I researched the const plans from Sire and found these items were to have been corrected. | |
05/26/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Met with the Building Official and showed him the pictures that we found today. He will address the situations within his department. He is reopening the permit for futher corrections. |