Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T17DV02183
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Had fire an upper unit and not able to remove power to the units that were damged by the fire. The building electrical was removed at a switch gear and will need to be checked by a electrician to have the power turned back on. The gas was removed at the meter due to the water heater is in the attic and not able to get to it and not sure what type of pilot it has and will need to be checked if damaged during the fire. The tenant was placed in a hotel by the management and will come back if the power can be turned back on. The manager signed the paper work and did the posting of Do Not Enter on the front window. Will check in 10 days. RV. | |
05/26/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Visited the site to try to determine how electric is fed to the building. This building has been installed with the old feed thru panels. It appears that the first panel has multiple taps for additional feeds to pass thru to the other units as per oringinal design. An Electrical Contractor will be needed to isolate the pass thrus's to be able to reenergize the unaffected units. Spoke to the owner and he will have the contractor call us. Owners electrician is on site doing the isolation taps. |