Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2017 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
THERE IS A NEW ROOF MOUNTED HVAC INSTALLED WITHOUT A PERMIT. MAIN DISCONNECT HAS CODE VIOLATIONS: UNUSED OPENINGS, NO LABELING, MISSING HARDWARE ON THE DOOR. THERE ARE EXPOSED CONDUCTORS IN 4 JUNCTION BOXES UNDER THE REAR PATIO. THERE IS A RECEPTACLE OUTLET UNDER THE DISCONNECT THAT IS NOT OUTDOOR RATED. THERE ARE MULTIPLE RECEPTACLES IN THE HOME THAT HAVE AN OPEN GROUND |