Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T17DV00594

Parcel: 12904224B


Addresses:

201 S NORRIS AV


Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T17DV00594

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2017 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T17CM03235 ISSUED AND EXPIRES ON 10-2017
CLOSE CASE
05/02/2017 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT ISSUED T17CM03235 ON 4-25-2017 INSTALL GROUNDING SYSTEM FOR UNIT DISCONNECTS, IDENTIFICATION AND PROPER LABELING (56 UNITS) AND 1 200AMP SERVICE UPGRADE T17DV00594
03/23/2017 INSP - FOLLOW UP CODE ENFORCE Approved SITE VISIT TO RETAKE PHOTOS OF MAIN SERVICE, REPAIRS TO LAUNDRY ROOM HAVE BEEN COMPLETED, ALL SUB PANELS NEXT TO MAIN SERVICE ARE 200 AMP TOOK PHOTOS
03/16/2017 INSP - FOLLOW UP CODE ENFORCE Approved INSPECTED THE ENTIRE PARKS ELECTRICAL EQUIPMENT CONSISTING OF 57 EQUIPMENT DISCONNECTS AND ONE SERVICE WITH MULTIPLE PANELS ON AT THE SERVICE LOCATION AND TWO DOWN STREAM PANELS. THERE ARE MULTIPLE CODE VIOLATIONS SUCH AS LACK OF A GROUNDING SYSTEMS AND THE INSTALL OF A 200 AMP DISCONNECT AND EQUIPMENT. DETAIL REPORT WILL FOLLOW. PERMITS REQUIRED. PHOTOS IN SIRE