Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T17DV00594
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T17CM03235 ISSUED AND EXPIRES ON 10-2017 CLOSE CASE |
|
05/02/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT ISSUED T17CM03235 ON 4-25-2017 INSTALL GROUNDING SYSTEM FOR UNIT DISCONNECTS, IDENTIFICATION AND PROPER LABELING (56 UNITS) AND 1 200AMP SERVICE UPGRADE T17DV00594 | |
03/23/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | SITE VISIT TO RETAKE PHOTOS OF MAIN SERVICE, REPAIRS TO LAUNDRY ROOM HAVE BEEN COMPLETED, ALL SUB PANELS NEXT TO MAIN SERVICE ARE 200 AMP TOOK PHOTOS | |
03/16/2017 | INSP - FOLLOW UP CODE ENFORCE | Approved | INSPECTED THE ENTIRE PARKS ELECTRICAL EQUIPMENT CONSISTING OF 57 EQUIPMENT DISCONNECTS AND ONE SERVICE WITH MULTIPLE PANELS ON AT THE SERVICE LOCATION AND TWO DOWN STREAM PANELS. THERE ARE MULTIPLE CODE VIOLATIONS SUCH AS LACK OF A GROUNDING SYSTEMS AND THE INSTALL OF A 200 AMP DISCONNECT AND EQUIPMENT. DETAIL REPORT WILL FOLLOW. PERMITS REQUIRED. PHOTOS IN SIRE |