Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | Fire call out. Arrived on scene and TFD had departed. TFD secured electric. TEP removed the meters for units 1&2. Southwest Gas reported no gas to the unit. Supervision was notified of all situations My findings are as follow: > The electric service showed hazardous conditions to unit #1. There were numerous electrical hazards at the service. Workmanship does not match work done at time of service upgrade. > Unit #2 had the fire damage to the interior. > The interior received excessive smoke damage. > The bedrooms were missing smoke alarms. There was evidence that they may have been present at the time of the fire. > The fire was in the rear bedroom at the electrical receptacle below the the window A/C unit. Bothe were damaged. > Egress was restricted due to storage and debris. > I met with the owner and issued NOV's for permits and emergency abatement. > Owner was upset at the disconnection of power to unit #1 due to electrical hazards. > Units were posted unsafe to occupy. > TFD Called Red Cross. |