Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T17CM09564
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2018 | MECHANICAL - FINAL | Approved | ||
09/25/2018 | MECHANICAL - FINAL | Partial Approval | REVIEW OF AIR BALANCE REPORT COMPLETED | |
09/06/2018 | MECHANICAL - FINAL | Partial Approval | paint exposed grease duct on roof. Provide 10ft separation between exhaust and makeup on type 2 Hood. | |
08/09/2018 | MECHANICAL - FINAL | Denied | BALANCE REPORT SHOWS HOOD SYSTEMS ARE NOT INSTALLED PER APPROVED PLANS | |
08/09/2018 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
08/08/2018 | MECHANICAL - FINAL | Not ready for Inspection | ||
08/07/2018 | MECHANICAL - FINAL | Not ready for Inspection | WAITING FOR AIR BALANCE REPORT APPROVAL FROM BOB SHERRY |