Permit: T17CM09544

Parcel: 138232720


Addresses:

749 W ACADIA DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/02/2018 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
01/31/2018 ELECTRIC - RECONNECT Denied OBTAIN AN UPGRADE PERMIT FOR SCOPE OF WORK PERFORMED
OMIT HAZARDOUS WIRING FRONT PORCH SEE NOTES FROM 1/4/18
RELOCATE SMOKE ALARMS MAY NOT BE WITHIN 36" FORCED AIR REGISTERS
01/08/2018 ELECTRIC - RECONNECT Denied SECURE PANEL TO CODE
PROVIDE LISTED PANEL DEADFRONT AND COVER
SUB PANEL NOT WIRED TO CODE
SMOKE ALARMS BEDROOMS AND HALLWAYS
01/04/2018 ELECTRIC - RECONNECT Denied OMIT HAZARDOUS WIRING FRONT PORCH
ACCESS TO UNIT REQUIRED
LEAVE MESSAGE WITH ACCESS INFO
NEXT DENIAL MAY RESULT IN A REFEE
01/03/2018 ELECTRIC - RECONNECT Denied no access
called at 1:10 pm, left messege , 1:30 no call back