Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2018 | ELECTRIC - FINAL | Approved | ||
| 01/29/2018 | ELECTRIC - FINAL | Denied | PLAN SHOWS TWO 3/4 EMT FROM PANELS TO INVERTERS, FIELD TECH PLACE 9 THWN WIRES IN ONE, ONE INCH EMT. DERATED THE WIRES AT 75 DEGRESS(70%) LOWERS THE BREAKER TO 25 AMPS. REQUESTED AN ENGINEERING PLAN CHANGE. |