Permit: T17CM09525

Parcel: 135040980

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/02/2018 ELECTRIC - FINAL Approved
01/29/2018 ELECTRIC - FINAL Denied PLAN SHOWS TWO 3/4 EMT FROM PANELS TO INVERTERS, FIELD TECH PLACE 9 THWN WIRES IN ONE, ONE INCH EMT. DERATED THE WIRES AT 75 DEGRESS(70%) LOWERS THE BREAKER TO 25 AMPS.
REQUESTED AN ENGINEERING PLAN CHANGE.