Permit: T17CM09426

Parcel: 110113610


Addresses:

2480 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/07/2018 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/08/2018 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1- DWV WATER TEST PROVIDED.
2- P.O.C. OF THE NEW BLDG. DRAIN TO THE EXISTING BLDG. DRAIN IS OKAY.
3-NOTE; THIS INSPECTION IS FOR THE FLOOR SINK IN THE DELI AREA ONLY.
05/07/2018 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1- RELOCATION OF THE FLOOR SINK IN THE BAKERY IS OKAY TO COVER.
2- DOMESTIC WATER DISTRIBUTION IN THE PONY WALLS IN THE SUSHI BAR IS OKAY. AIR PRESSURE TEST PROVIDED.
3- DWV WATER TEST PROVIDED.
4- NOTE; SHALL VERIFY THE FINAL CONNECTION OR TERMINATION OF THE SANITARY VENT FOR THE SUSHI BAR. THIS INSPECTION IS FOR THE SUSHI BAR AREA ONLY.
05/02/2018 PLUMBING - ROUGH, SOIL Partial Approval SUSHI ROUGH AND SUPPLY OK TO BACKFILL
04/27/2018 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1- DWV WATERV TEST PROVIDED.
2- P.O.C. OF THE NEW BLDG. DRAIN TO THE EXISTING BLDG. DRAIN IS OKAY.
3- THIS INSPECTION WAS FOR THE CWV SYSTEM LOCATED IN AISLE #10 AND THE FLOOR SINK LOCATED AT THE BEVERAGE STATION ONLY.
4- OKAY TO BACKFILL TRENCH.
04/26/2018 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL CONNECT THE CWV BRANCH LINES HORIZONTALLY TO THE CWV TRUNK LINE. REFERENCE SECTION 915 2012 IPC.
2- RETEST THE SYSTEM.


*