Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM09404
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2018 | FIRE - FINAL | Approved | -needs a dedicated circuit for fire panel. will verify on phase 2. -removed slidebolts from security doors while on site. -removed all mag locks and hardware from exit doors. not allowed in F-1's. -will call us to place lock box key. -added 12" address numbers to bldg. |
|
| 03/15/2018 | FIRE - FINAL | Partial Approval | PA. OK to obtain TCO for phase 1. Reinspection fee added and must be paid prior to next inspection. Still needs the following for final. 1) need sprinkler monitoring. hire fire alarm contractor. 2) mount knox box. provide key. 3) mount spare head box next to inspectors test. OK to obtain TCO for phase one once the sprinkler system and back flows are inspected and all deficiecies on those two items are corrected. Need to secure control valves with chains & lock until they are elec supervised. All items shall be completed prior to full CofO. |
|
| 03/12/2018 | FIRE - FINAL | Cancelled | ||
| 03/02/2018 | FIRE - FINAL | Partial Approval | 1) no sprink work in phase 1. needs to replace all escutcheons. 2) need annual fire sprinkler inspection report. all deficiencies shall be corrected. 3) need 5yr internal OS&Y inspection report. 4) need current backflow inspection/certification report for fire backflows. 5) need sprinkler monitoring. hire fire alarm contractor. 6) mount extinguishers. 7) order knox box and mount. provide key. OK to obtain TCO for phase one once the sprinkler system and back flows are inspected and all deficiecies on those two items are corrected. Need to secure control valves with chains & lock until they are elec supervised. All items shall be completed prior to full CofO. |