Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/17/2018 MECHANICAL - FINAL Approved test and balance report has been submitted to the city
08/28/2018 MECHANICAL - FINAL Denied BALANCE REPORT SHOWS FAN COILS 29% TO 100% SHORT OF OUTSIDE AIR. ENGINEER'S EVALUATION REQUIRED.
08/27/2018 MECHANICAL - FINAL Partial Approval IVRS - Inspection : AIR BALLANCE REPORT SENT BOB SHERRY BY WAY OF RECORDS
12/21/2017 MECHANICAL - FINAL Prior to Final Inspectn AIR BALANCE REPORT REQUIRED