Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2018 |
MECHANICAL - FINAL |
|
Approved |
test and balance report has been submitted to the city |
| 08/28/2018 |
MECHANICAL - FINAL |
|
Denied |
BALANCE REPORT SHOWS FAN COILS 29% TO 100% SHORT OF OUTSIDE AIR. ENGINEER'S EVALUATION REQUIRED. |
| 08/27/2018 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection : AIR BALLANCE REPORT SENT BOB SHERRY BY WAY OF RECORDS |
| 12/21/2017 |
MECHANICAL - FINAL |
|
Prior to Final Inspectn |
AIR BALANCE REPORT REQUIRED |