Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T17CM09380
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2018 | FRAMING | Approved | IVRS - Inspection :* | |
01/23/2018 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- DWV WATER TEST FOR THE SECOND FLOOR RESTROOMS PROVIDED. 2- P.O.C. OF THE NEW BLDG. DRAIN TO THE EXISTING BLDG. DRAIN IS OKAY. 3- OVERHEAD AND IN WALL DOMESTIC WATER DISTRIBUTION FOR THE SECOND FLOOR RESTROOMS IS OKAY. 4- SHALL PROVIDE THE APPROVED SCREWS FOR THE METAL STUDS. 5- SHALL PROVIDE KICKERS EVERY 4 FEET ON PARTION WALLS. * |
|
12/28/2017 | FRAMING | Partial Approval | 110 OK |