Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/13/2018 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/30/2018 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999
1- REFERENCE SECTION 230.24 NEC 2011 FOR ABOVE ROOF CLEARANCE.


*
01/22/2018 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999
1- RISER MAST IS LOCATED TO LOW TO THE ROOF. THE NEC REQUIRES IT TO BE LOCATED EIGHT FEET ABOVE THE ROOF WHEN THE CONDUCORS TRAVERSE THE ROOF.


*
01/10/2018 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
CLEAR ELECTRIC INCR