Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T17CM09190
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2019 | PLUMBING - ABOVE CEILING | Approved | ||
04/30/2019 | PLUMBING - ABOVE CEILING | Partial Approval | All Above ceiling approved in patient treatment area, OK to set ceiling tiles. | |
04/18/2019 | PLUMBING - ABOVE CEILING | Partial Approval | MRI, x-ray, CT, control room above ceiling OK | |
02/20/2019 | PLUMBING - ABOVE CEILING | Partial Approval | Overhead for MRI and walls with Martin. MRI connection, Isolated, gauge for vacuum at 60 PSI. Then 3 gauges at hallway, Oxy, Med Air, and Vacuum, all at 60 PS |
|
10/29/2018 | PLUMBING - ABOVE CEILING | Partial Approval | All North rooms from control room to kitchen ok. | |
10/25/2018 | PLUMBING - ABOVE CEILING | Partial Approval | Same rooms as in Intermediate Plumbing, 122,136,7,119,120,110,111,112,TR4,TR3101,105,100,106,127,126,125,ER,123,Patient Restrooms,Break Room, Patient Rooms 1,2,3,5, Phys Rm3,141,132, and 129. |