Permit: T17CM09187

Parcel: 11105262A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
09/06/2018 FIRE - FINAL Approved APPROVAL SENT TO RECORDS
08/29/2018 FIRE - FINAL Partial Approval Ok to fixture but not occupy or open for buisness and or train staff
Add 2 fire extinguishers
Need FACP Inside sign
Need FDC sign
Address required on th blackledge side
Paint the fire riser
06/05/2018 FIRE - FINAL Not ready for Inspection Note for OH... OH approved however permission not granted to cover ceiling. Need either head moved or central vaccuum pvc moved head is less than 4 inches away. There was also duct work touching a few sprinklers that need to be 4 inches or greater. Also insulation needs to be removed from sprinkler heads.
04/20/2018 FIRE - FINAL Not ready for Inspection No Access to Office, called Contractor, No Answer. At 2pm Contractor called back at 3pm, said he would reschedule.