Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2018 | FIRE - FINAL | Approved | ||
| 07/31/2018 | FIRE - FINAL | Partial Approval | Fire alarm approved by state fire marshal Still need the following for full approval: 1) add panic hardware to west, chain link, gates. 2) add panic hardware to SE metal gate. 3) add panic hardware to west exit door from auditorium. |
|
| 07/05/2018 | FIRE - FINAL | Partial Approval | Still needs a full fire final. This was an inspection for TCO only. Approved to obtain TCO for multipurpose room, library, admin area, east hall with bathrooms. TCO is for "B"use only, not for "E"use. The following items will be completed for TCO. -All ceiling tiles installed in TCO area. -Secure exterior gate from library in open position until panic hardware is installed. -Add "not an exit" to doors discussed. -Secure west hall from public. -Add EM lights and exit signs to stage. -May need to add addition EM lights to east hall prior to full final. -Secure doors in hall from public. All doors that lead to other classrooms and courtyards. |
|
| 06/26/2018 | FIRE - FINAL | Partial Approval | -knox box -mount extinguishers -reinspection fee added. must be paid prior to next inspection. -add door to computer room that leads to the exterior. 1018.1 #1. |