Permit: T17CM09083

Parcel: 137315160


Addresses:

4911 S RIVER RUN DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/05/2018 FRAMING Approved
03/02/2018 FRAMING Denied 1 nail 2nd fl shear wall sole plates 2block combustion vents 3 complete detail 306 4 provide access to ufer clamp 5 protect electric conductors within 6' of attic access
03/01/2018 FRAMING Cancelled
02/23/2018 FRAMING Denied 1 shim bearing headers 2 nail 2nd floor shear wall sole plates per shear schedule 3 block combustion vents in garage 4 install gble end braces per detail 306 5 install anchor bolts within 12" of plate end in garage n wall 6 seall all penetrations in lqth 7 provide access to ufer clamp 8 ground metql box in master bath 9 complete electric in attic, master bath and front edroom 10 protect electric conductors within 6' of attic access 11 complete line sets 12 install insulation shield on w/h b vent in attic 13 cripple a/c return in master