The login landing page when selecting 'View' is still occurring and is still pending further investigation.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/06/2018 |
ELECTRIC - FINAL |
|
Approved |
|
| 02/05/2018 |
ELECTRIC - FINAL |
|
Partial Approval |
PV INSTALLATION IS OK, BUT THE MAIN PANEL DOES NOT HAVE A MAIN BREAKER. EITHER INSTALL A MAIN BREAKER IN THE EXISTING PANEL OR REPLACE IT WITH A NEW PANEL THAT HAS A MAIN BREAKER. AS AN ALTERNATIVE, IF THE SYSTEM CAN BE REBUILT SO THAT IT REQUIRES SIX OR LESS THROWS OF A SWITCH TO SHUT DOWN THE ENTIRE BUILDING, THAT WILL BE ACCEPTED. |