Permit: T17CM08930

Parcel: 114461730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/06/2018 ELECTRIC - FINAL Approved
02/05/2018 ELECTRIC - FINAL Partial Approval PV INSTALLATION IS OK, BUT THE MAIN PANEL DOES NOT HAVE A MAIN BREAKER. EITHER INSTALL A MAIN BREAKER IN THE EXISTING PANEL OR REPLACE IT WITH A NEW PANEL THAT HAS A MAIN BREAKER. AS AN ALTERNATIVE, IF THE SYSTEM CAN BE REBUILT SO THAT IT REQUIRES SIX OR LESS THROWS OF A SWITCH TO SHUT DOWN THE ENTIRE BUILDING, THAT WILL BE ACCEPTED.