Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2018 | ELECTRIC - FINAL | Approved | ||
| 03/28/2018 | ELECTRIC - FINAL | Denied | NEED LADDER FOR ROOF ACCESS. SUB PANEL NEEDS WATER PROOF FITTINGS ON LBS ENTERING PANEL ABOVE BOTTOM OF BUSS BARS SUB PANEL COVER DOESNT LATCH PROPERLY GAS BOND REQUIRED LATCH ON SUB PANEL S/B SPRING LOADED |
|
| 01/31/2018 | ELECTRIC - FINAL | Not ready for Inspection | GAS BOND CAN BE MADE WITH JUMPER AT WATER HEATER. CHECK FOR GAS BOND AT FINAL |