Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM08867
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2019 | PLUMBING - INTERMEDIATE | Denied | 1- Shall provide the required shield plate for the sole plate at the 3 inch waste and vent pipe. 2- Shall provide a block support for the 2 inch horizontal vent for the kitchen sink. 3- Shall provide a minimum of 12 inch separation of the water line from the can light. 4- Shall provide a sanitary tee for the lavatory trap arm. 5- Shall provide a minimum is two times the pipe size diameter of trap arm distance on clothes washer. 6- Re test on he DWV system. |
|
01/23/2019 | PLUMBING - INTERMEDIATE | Approved | ||
01/18/2019 | PLUMBING - INTERMEDIATE | Partial Approval | Leak at bathroom sink area | |
01/16/2019 | PLUMBING - INTERMEDIATE | Partial Approval | secure pex and ABS piping in walls where loose. ABS piping needs to be under test at time of inspection |