Permit: T17CM08867

Parcel: 124090560


Addresses:

1815 E 9TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T17CM08867

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2019 ELECTRIC - INTERMEDIATE Approved Clearance TEP-INCR. Customer is installing new 200 amp service at guest quarters, and feeding back to existing service which will become a sub-panel with meter socket blanked. This change to revised plans accommodates TEP’s request to re-route existing overhead conductors that are now in violation of clearance requirements due to proximity to new structure. Builder will run feeders of 1/0 copper with 150 amp breaker, which meets Code.
04/02/2019 ELECTRIC - INTERMEDIATE Partial Approval NEED REINSPECTION
01/18/2019 ELECTRIC - INTERMEDIATE Approved
01/16/2019 ELECTRIC - INTERMEDIATE Partial Approval finish terminating Romex at panel. Finish receptacles in kitchen