Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM08687
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2018 | PLUMBING - INTERMEDIATE | Approved | ||
11/20/2018 | PLUMBING - INTERMEDIATE | Partial Approval | Rooms; 1202, 1203, 1204, 1205, 1206, 1207, 1208, 1209. Column Line 7 to the East for M, P , and E at above ceiling For 1st and second floors. | |
11/08/2018 | PLUMBING - INTERMEDIATE | Partial Approval | rooms 102, 103, 104, 1204, 1202, 2700 A, 2700 B, 2700 through 2715 walls okay. Add nail plates or protect PVC piping in several spots before covering. | |
11/06/2018 | PLUMBING - INTERMEDIATE | Not ready for Inspection | ||
11/02/2018 | PLUMBING - INTERMEDIATE | Partial Approval | 1st floor east of C.L. 7 north of corr ok. | |
10/20/2018 | PLUMBING - INTERMEDIATE | Partial Approval | PA for 1st and 2nd floor at column line 7, west. This includes the Monitors and the east most monitors. | |
10/10/2018 | PLUMBING - INTERMEDIATE | Partial Approval | 1st floor C.L. 7,8,9 north of corr ok | |
09/28/2018 | PLUMBING - INTERMEDIATE | Partial Approval | South side from C.L. 6 to west 1st and 2nd floors ok. | |
09/17/2018 | PLUMBING - INTERMEDIATE | Not ready for Inspection | walked with contractor |