Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T17CM08682
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2018 | FRAMING | Approved | ||
01/12/2018 | FRAMING | Denied | 1. FHA STRAP MAIN GAS RISER OVER-BORE, AND ABS TOP PLATE OVER BORE. 2. MOVE PEX 12" FROM CAN LIGHTS. 3. SUPPORT 4 GANG IN KITCHEN. 4. REDO GAS TEST. - 1.5 LBS AT PRESENT. 5.FINISH WIRING AT STOVE. 6. NEED RFI FROM ENGINEER FOR DRYER DUCT OVER-BORE IN 2X6 TOP PLATE OF SHEAR WALL. 7. NEED DWV AND WATER PRESSURE. 8. NAIL OFF FHA STRAP AT HVAC LINE OVER-BORE. 9. FINISH OUTLET WIRING IN N.E. AND N.W. BEDROOMS. 10. SCREW TOILET FLANGES TO FLOOR |