Permit: T17CM08313

Parcel: 121080600


Addresses:

6208 E LEE ST #02

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/30/2018 PLUMBING - ROUGH, SOIL Approved
11/23/2018 PLUMBING - ROUGH, SOIL Denied 1- Shall provide the approved two way clean out fittings, San tee not approved.
2- No dridging allowed on horizontal soil lines, shall provide a firm bed under piping.
3- Shall provide directional fittings for the water closet and shower.
4- Shall provide a water test on the DWV system.