Permit: T17CM08232

Parcel: 13101040A


Addresses:

4984 E 22ND ST

Inspection Status: Passed

Inspection History: COT - LCEL - Service UpgradeĀ 

Date Description Inspector Results Comments
05/15/2019 COT - LCEL - Service UpgradeĀ  GWEST Approved Entered by CBELL1 - Ufers connected, Gas is bonded, Water is bonded. All sized in accordance with the NEC based on SE Cable size. Main bonding jumper is attached to the can.
05/09/2019 COT - LCEL - Service UpgradeĀ  GWEST Correction Required Entered by VFLORES1 - Install water bond and gas bond for TEP Clearance