Permit: T17CM08232

Parcel: 13101040A


Addresses:

4984 E 22ND ST

Inspection Status: Passed

Inspection History: COT - LCEL - Construction Power

Date Description Inspector Results Comments
05/15/2019 COT - LCEL - Construction Power GWEST Approved Entered by CBELL1 - Ufers connected, Gas is bonded, Water is bonded. All sized in accordance with the NEC based on SE Cable size. Main bonding jumper is attached to the can. TEP was called for Clearance on this new and separate Switch Gear. Spoke with Natalie, ECO.
05/09/2019 COT - LCEL - Construction Power GWEST Correction Required Entered by VFLORES1 - Install water bond and gas bond for TEP Clearance