Inspection Status: Passed
Inspection History: COT - LCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 08/04/2022 |
COT - LCME - Mechanical Final |
RSHERRY |
Approved |
Entered by RSHERRY1 - REVIEW OF AIR BALANCE REPORT COMPLETED |
| 04/11/2022 |
COT - LCME - Mechanical Final |
RSHERRY |
Correction Required |
Entered by RSHERRY1 - THE MINIMUM EXHAUST FLOW RATE FOR ANIMAL HOLDING ROOMS (EF-2) IS 0.9 CFM PER SF |
| 02/10/2022 |
COT - LCME - Mechanical Final |
RSHERRY |
Correction Required |
Entered by RSHERRY1 - EXHAUST FLOW RATES FOR EF-1 & EF-2 MORE THAN 10% BELOW REQUIREMENT |
| 02/09/2022 |
COT - LCME - Mechanical Final |
ESTEVENS |
Partial Approval |
Entered by VVERA1 - Partial. Pending air balance report for last phase. |
| 04/28/2021 |
COT - LCME - Mechanical Final |
DMUNIZ |
Partial Approval |
Entered by RSALDAT1 - Partial, phase 2 mechanical complete. |
| 04/22/2021 |
COT - LCME - Mechanical Final |
WGALLAGHER |
Partial Approval |
Entered by VLEON1 - PARTIAL APPROVAL FOR SECOND PHASE ONLY, 2 FURNACES REQIRE REROUTED EXHAUST PIPES IN SECOND STORY DOGHOUSE AREA |
| 12/23/2019 |
COT - LCME - Mechanical Final |
RCHANDLER |
Partial Approval |
Entered by SFLORES2 - Phase one |
| 12/11/2019 |
COT - LCME - Mechanical Final |
RSHERRY |
Partial Approval |
Entered by RSHERRY1 - REVIEW OF AIR BALANCE REPORT COMPLETED |
| 11/21/2019 |
COT - LCME - Mechanical Final |
MRAMBER |
Not ready for Inspection |
Entered by DMERANZ1 - Provide approved air balance report. Serviceable equipment on roof within 10 foot of roof edge must have guard rails. Line set insulation on roof must be coded for UV protection. Remove gooseneck From water heater exhaust, install per manufacture. |