Permit: T17CM08232

Parcel: 13101040A


Addresses:

4984 E 22ND ST

Inspection Status: Passed

Inspection History: COT - LCME - Mechanical Final 

Date Description Inspector Results Comments
08/04/2022 COT - LCME - Mechanical Final  RSHERRY Approved Entered by RSHERRY1 - REVIEW OF AIR BALANCE REPORT COMPLETED
04/11/2022 COT - LCME - Mechanical Final  RSHERRY Correction Required Entered by RSHERRY1 - THE MINIMUM EXHAUST FLOW RATE FOR ANIMAL HOLDING ROOMS (EF-2) IS 0.9 CFM PER SF
02/10/2022 COT - LCME - Mechanical Final  RSHERRY Correction Required Entered by RSHERRY1 - EXHAUST FLOW RATES FOR EF-1 & EF-2 MORE THAN 10% BELOW REQUIREMENT
02/09/2022 COT - LCME - Mechanical Final  ESTEVENS Partial Approval Entered by VVERA1 - Partial. Pending air balance report for last phase.
04/28/2021 COT - LCME - Mechanical Final  DMUNIZ Partial Approval Entered by RSALDAT1 - Partial, phase 2 mechanical complete.
04/22/2021 COT - LCME - Mechanical Final  WGALLAGHER Partial Approval Entered by VLEON1 - PARTIAL APPROVAL FOR SECOND PHASE ONLY, 2 FURNACES REQIRE REROUTED EXHAUST PIPES IN SECOND STORY DOGHOUSE AREA
12/23/2019 COT - LCME - Mechanical Final  RCHANDLER Partial Approval Entered by SFLORES2 - Phase one
12/11/2019 COT - LCME - Mechanical Final  RSHERRY Partial Approval Entered by RSHERRY1 - REVIEW OF AIR BALANCE REPORT COMPLETED
11/21/2019 COT - LCME - Mechanical Final  MRAMBER Not ready for Inspection Entered by DMERANZ1 - Provide approved air balance report. Serviceable equipment on roof within 10 foot of roof edge must have guard rails. Line set insulation on roof must be coded for UV protection. Remove gooseneck From water heater exhaust, install per manufacture.