Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T17CM08103
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2018 | BUILDING - FINAL | Approved | Chlorination and Mechanical Testing Approved by R Sherry | |
| 04/06/2018 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- DOOR WAS LOCKED, NO ACCESS. * |
|
| 03/23/2018 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE FLOOR SINK GRATES FOR ALL FLOOR SINKS. 2- SHALL SECURE THE TRIPPLE COMPARTMENT SINK AND PREP SINK TO WALL. 3- SHALL CAULK ALL FIXTURES. 4- SHALL REPLACE OR REMOVE THE GFI RECEPTICALS IN RESTROOMS. 5- SHALL LOCATE THE ACCESSIBLE WATER CLOSET 16 TO 18 INCHES OF SIDE WALL CLEARANCE. 6- SHALL PROVIDE A 1022 BACVKFLOW PREVENTER FOR THE ICE MAKER. 7- SHALL SECURE THE WATER HEATER EXPANSION TANK. 8- SHALL PROVIDE A OFF SET TAIL PC PROTECTION ON THE ACCESSIBLE LAVATORY. 9- SHALL PROVIDE THE REQUIRED ACCESSIBLE SIGNAGE FOR THE RESTROOM WITH THE INTERNATIONAL SYMBOL. 10 SHALL PROVIDE A WATER CHLORINATION REPORT FOR THE DOMESTIC WATER DISTRIBUTION. 11- SHALL PROVIDE A PERMANATE ANZUL VALVE LABEL ON THE CEILING TILE LOCATION. * |