Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM08057
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2018 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/24/2018 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE 11/4 SUPPLY TO THE FIRST TEE TO THE WATER HEATER SUPPLY THEN REDUCE DOWN TO 3/4 INCH AS PER THE APPROVED PLANS. 2- SHALL STRAP DOWN THE SUPPLY TO THE REAR HOSE BIB. * |
|