Permit: T17CM08012

Parcel: 114540180

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/12/2018 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/10/2018 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL REMOVE ALL FERNCO COUPLINGS IN WALL AND PROVIDE SOLVENT WELD FITTINGS OR MISSION SPECIALTY COUPLINGS.
2- SHALL BRAZE THE PERMANETE CAP BELOW THE FLOOR ON WATER LINE IN BATHROOM.
4- SHALL POSITION THE DOUBLE COMBO ON THE REVENT IN THE MASTER BATHROOM.


*