Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T17CM07889
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2018 | ELECTRIC - FINAL | Approved | ||
11/14/2018 | ELECTRIC - FINAL | Denied | GFI required at lab sink, label electrical panel L5, maximum overcurrent protection on air handlers is 15 A. |