Permit: T17CM07642

Parcel: 104090850

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T17CM07642

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2017 ELECTRIC - RECONNECT Approved APPROVED
11/24/2017 ELECTRIC - RECONNECT Not ready for Inspection
10/11/2017 ELECTRIC - RECONNECT Denied NEUTRAL AND GROUND NEED SPLITBOLT.
WIRE (seu cable) NEEDS A BUSHING.
WIRE NOT SIZED FOR 100 AMPS TO SUB PANEL.
10/10/2017 ELECTRIC - RECONNECT Denied 1) USNIG GROUNDED OUTLETS ON AN UNGROUNDED SYSTEM.
2) PROPERLY INSTALL GROUNDING ELECTODE CONDUCTOR TO GROUND BUS BAR.
3) PROPERLY INSTALL NEUTRAL WIRE TO GROUND BUS BAR
4) SMOKE DETECTORS MUST NOT BE LESS THAN 12" FROM CEILING