Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T17CM07642
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2017 | ELECTRIC - RECONNECT | Approved | APPROVED | |
| 11/24/2017 | ELECTRIC - RECONNECT | Not ready for Inspection | ||
| 10/11/2017 | ELECTRIC - RECONNECT | Denied | NEUTRAL AND GROUND NEED SPLITBOLT. WIRE (seu cable) NEEDS A BUSHING. WIRE NOT SIZED FOR 100 AMPS TO SUB PANEL. |
|
| 10/10/2017 | ELECTRIC - RECONNECT | Denied | 1) USNIG GROUNDED OUTLETS ON AN UNGROUNDED SYSTEM. 2) PROPERLY INSTALL GROUNDING ELECTODE CONDUCTOR TO GROUND BUS BAR. 3) PROPERLY INSTALL NEUTRAL WIRE TO GROUND BUS BAR 4) SMOKE DETECTORS MUST NOT BE LESS THAN 12" FROM CEILING |