Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T17CM07552
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2018 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/01/2018 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |
|
12/27/2017 | MECHANICAL - FINAL | Denied | SEE PRIOR NOTES. LINE SETS TO BE SUOORTED EVERY 10 FT VERTICLE AND 6FT HORIZONTALLY. PVC TO BE PRIMED AND GLUED. PROTECT ARMAFLEX FROM SUN. NEED ROOF ACCESS. NEED OVERFLOW SENSOR. |
|
10/19/2017 | MECHANICAL - FINAL | Denied | PROVIDE AN OVERFLOW SENSOR. PROVIDE A TRAP IN CONDENSATE DRAIN. PVC VENTING AT FURNACE IS FALLING APART AND WASN'T GLUED. PROVIDE A PERMIT FOR NEW FURNACE. PROVIDE TAMPER PROOF CAPS AT CONDENSOR. SECURE AND SUPPORT LINE SET. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. CONDENSOR OVERFUSED. FURNACE EXHAUST MUST BE TERMINATED THROUGH THE ROOF. PROVIDE ROOF ACCESS. DID NOT SEE CONDENSATE TERMINATION. |
|
10/18/2017 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |