Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2018 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2018 | PLUMBING - FINAL | Partial Approval | REVIEW OF WATER CHLORINATION REPORT COMPLETED | |
| 06/11/2018 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE A 1022 IN LINE BACKFLOW PREVENTER FOR THE COFFEE AND ICE MAKER. 2- SHALL PROVIDE A TRAP PRIMER OR TRAP GUARD FOR THE FLOOR DRAIND AS PER PLAN. 3- SHALL EXTEND THE VACUUM RELIF VALVE ABOVE THE WATER HEATER AND AS PER MANUFACTURER'S INSTALLATION STANDARDS. 4- SHALL CAULK ALL SINKS. 5- SHALL RUN EACH COMPARTMENT TO BE INDEPENDENT INDIRECT WASTE LINES FOR THE TRIPPLE COMPARTMENT SINK. * |
|
| 02/27/2018 | PLUMBING - FINAL | Prior to Final Inspectn | WATER CHLORINATION REPORT REQUIRED |