Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2017 | MECHANICAL - FINAL | Approved | ||
| 10/05/2017 | MECHANICAL - FINAL | Not ready for Inspection | THIS IS AN UNPROFESSIONAL INSTALLATION. UNIT AND ITS COMPONANTS WILL BE REPLACED BY LICENSED CONTRACTOR. 1. ROOF UNIT IS NOT ON SKIDS. 2. CROSS CONNECTION FROM CONDENSATE DRAIN TO SEWER VENT. HAZARDOUS 3. WRONG SIZE UNIT AND DUCT WORK. 4. NEW UNIT BLOCKED ACCESS TO FURNACE PLUG. 5.TAPE BLOCKED THE PROPER FUNCTION OF THE FURNACE B VENT AND JOINTS ARE NOT SCREWED. HAZARDOUS |